STATE 535

Fan defect detected during fan controller self test

Behaviors

Target speed of one or both fans not reached

Fan not functioning, possibly power derating

Status Code Class 5

Class 5 status codes (state codes that start with a five, i.e., 5xx), do not generally interfere with feeding energy into the grid, but can cause restrictions. These status codes are displayed until they are acknowledged by pressing a key, however the inverter continues to operate normally in the background.

STATE 535 applies to:

CL

CL

Solutions for this Error

Remedies

  • Check inverter location, clearance of the ventilation ports. Clean air inlets and ensure exhaust ports have proper space.
  • Check STATE FAN in the Setup menu to determine which fan is affected
  • If this issue persists, the next steps include inspecting internal inverter components and their cabling by a trained Fronius Service Provider to further diagnose this specific issue. Defective components or the device itself may need to be replaced.

Get Help with this Error:

The best point of contact is your original installer
If the orginal installer is no longer available, contact a local Fronius Service Provider