fronius logo
Froniuis displaySTATE 540

STATE 540

Overcurrent detected by fan controller

Behaviors

Target speed of one or both door fans not reached

Door fan not functioning, possibly power derating

Status Code Class 5

Class 5 status codes (state codes that start with a five, i.e., 5xx), do not generally interfere with feeding energy into the grid, but can cause restrictions. These status codes are displayed until they are acknowledged by pressing a key, however the inverter continues to operate normally in the background.

STATE 540 applies to:

CL

CL

Solutions for this Error

Remedies

  • Check inverter location, clearance of the ventilation ports. Clean air inlets and ensure exhaust ports have proper space.
  • If this issue persists, the next steps include inspecting internal inverter components and their cabling by a trained Fronius Service Provider to further diagnose this specific issue. Defective components or the device itself may need to be replaced.

Get Help with this Error:

The best point of contact is your original installer
If the orginal installer is no longer available, contact a local Fronius Service Provider

DENVER RESIDENTS: Is your system located in the Denver, CO metro area? CONTACT US

BACK